Glands > COMET FLAMEPROOF TYPE DOUBLE COMPRESSION CABLE GLAND


Previous


Next

 
 

Indoor Or Outdoor Gland For Single Wire Armoured Cables

Gland reference

Cable dimensions

Gland dimensions

  Diameter Armour
wire
diameter
Entry thread Across
flats

(E)
Across
corners

(F)
Under
armour
(A)
Overall
Diameter
(B)
Entry

(C)
Length

(D)
size mm mm mm inch mm mm mm
CBF01SS 8.0 12.0 0.8/1.4 3/4" 25.0 21.0 23.5
CBF01S 10.0 16.5 0.8/1.4 3/4" 25.0 25.0 29.0
CBF01 12.0 18.0 0.8/1.4 3/4" 25.0 28.0 32.0
CBF01A 12.0 18.0 0.8/1.4 1" 25.0 28.0 32.0
CBF02 14.0 20.0 0.8/1.4 1" 25.0 31.5 36.5
CBF02A 14.0 20.0 0.8/1.4 3/4" 25.0 31.5 36.5
CBF03 17.0 23.0 0.8/1.4 1" 25.0 32.0 37.0
CBF04 20.0 26.0 0.8/1.4 1" 25.0 38.0 44.0
CBF04A 20.0 26.0 0.8/1.4 11/4" 25.0 38.0 44.0
CBF05 24.0 30.0 0.8/1.4 11/4" 25.0 41.0 47.0
CBF05A 24.0 30.0 0.8/1.4 11/2" 25.0 41.0 47.0
CBF06 27.0 33.0 0.8/1.4 11/2" 25.0 47.0 54.0
CBF06A 27.0 33.0 0.8/1.4 11/4" 25.0 47.0 54.0
CBF07 30.0 37.0 0.8/1.4 11/2" 25.0 52.0 58.0
CBF08 35.0 41.0 0.8/1.4 2" 25.0 56.0 64.0
CBF09 40.0 46.0 0.8/1.4 2" 25.0 59.0 67.0
CBF010 46.0 52.0 0.8/1.4 2" 25.0 67.5 77.0
CBF010A 46.0 52.0 0.8/1.4 21/2" 25.0 67.5 77.0
CBF011 54.0 60.0 0.8/1.4 21/2" 25.0 80.0 92.0
CBF012 60.0 67.0 0.8/1.4 3" 25.0 85.0 98.0
CBF013A 66.0 72.0 0.8/1.4 3" 25.0 90.0 99.0
CBF013 72.0 78.0 0.8/1.4 31/4" 25.0 99.0 113.0
CBF014 78.0 84.0 0.8/1.4 31/2" 25.0 108.0 122.0
CBF015 88.0 94.0 0.8/1.4 4" 25.0 117.0 131.0
CBF016 98.0 105.0 0.8/1.4 41/2" 25.0 130.0 145.0

Cable

Application

For use in hazardous atmosphere and most climatic condition. Flameproof glands are suitable for GASI, IIA, IIB, IIC, Ex-"d", Ex-"e"
 

Specification

Gland consist of checknut 1, gland  body 2, neoprene inner ring 3, armour clamping cone 4, armour clamping ring 5, amour clamping nut 6,neoprene outer ring 7, skid washer 8, outer seal nut 9. All metal parts are made of brass accurately machined for ease of assembly.

Approvals

COMET flameproof glands are approved by Central Mining Research Center, Dhanbad. (Approved by CMRI, BIS, DGFASLI, CCOE - NAGPUR)

Extras

Shrouds and Earth tags are supplied separately and should be specified when ordering the gland.

Fitting Sequence:

Fitting Sequence
(a) Screw item 2 into apparatus (secure with item 1 if plain hole entry.)
(b) Pass item 9,8,7,6 respectively over cable before commencing to strip oversheath.
(c) Remove oversheath and pass item 5 over exposed armour.
(d) Cut armour to length, lift wire ends, pass item 4 over exposed bedding and beneath armour.
(e) Pass item 3 over exposed bedding.
(f) Pass cable end through item 2.
(g) Engage item 6 and 2 and tighten up.
(h) Engage item 9 and 6 and tighten up.
 
 

 

 




 

2005 Comet Cable Gland & Terminals.  All Rights Reserved.